1 temperature sensor (battery), 2 54v dc output with alarm-indicating fuses, 3 battery circuit breaker – Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 16: 4 54v dc output terminal block, 5 battery connector

Advertising
background image

0300072-J0 RevA

Page 12 of 46

2.6.4.1 T

EMPERATURE

S

ENSOR

(B

ATTERY

)

Temperature probe input for battery temperature compensation.

2.6.4.2 54V

DC

O

UTPUT WITH ALARM

-

INDICATING

F

USES

4 outputs are available on the distribution unit, protected by alarm-indicating fuses. The available fuse ratings

are 2A, 5A and 10A and these can be ordered from Alpha Technologies.
When a fuse is blown, a coloured dot indicates the circuit is open. The fuses are numbered from 1 to 4, fuse 1

corresponding to the most left DC output and so on from left to right.

2.6.4.3 B

ATTERY

C

IRCUIT

B

REAKER

If the battery is correctly connected, the user can set (close) the LVD by pushing the button of the battery circuit

breaker. When the LVD is active (closed), the green “LVD OK” LED on the front of the distribution unit and the

green “LVD OK” LED on the front of the controller illuminate. By pulling the button of the battery circuit breaker,

the LVD will open and the battery is disconnected from the system. Both green LEDs will then extinguish.
The status of the battery circuit breaker is monitored by the controller and can be used as an alarm source.

CAUTION

CAUTION! Before plugging and unplugging the battery connector, the user should pull the

battery circuit breaker and check whether the LVD is non-active (open) to avoid damaging the

battery connector contacts.

2.6.4.4 54V

DC

O

UTPUT

T

ERMINAL

B

LOCK

The four DC outputs are located below the alarm-indicating fuses. Each output is protected by a single pole

alarm-indicating fuse (see section 2.6.4.2). Please observe the polarity of the DC output connector:

Out 1

Out 2

Out 3

Out 4

+

-

+

-

+

-

+

-

Please observe the following wiring specifications:

Stripping length: 10 mm

Minimum conductor cross section: 0.2 mm² stranded

Maximum conductor cross section: 2.5 mm² stranded

2.6.4.5 B

ATTERY

C

ONNECTOR

Please observe the polarity of the battery. The battery connector polarity is indicated on the front plate:

Battery

+

-


The battery connector is a 2-pole Phoenix contact PC 4/2-G-7,62 (18 04 79 7)
The battery mating connector reference is Phoenix contact PC 4/ 2-ST-7,62 (18 04 90 4)
The battery capacity is limited by the interrupting capacity of the 20A battery circuit breaker and should not

exceed 62Ah.

CAUTION

CAUTION! Before plugging and unplugging the battery connector, the user should pull the

battery circuit breaker and check whether the LVD is non-active (open) to avoid damaging the

battery connector contacts