Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 25

Advertising
background image

0300072-J0 RevA

Page 21 of 46

8

Dig_Out2_n_closed

Normally closed contact of potential free alarm 2

X112

Name

Remarks

1

Dig_Out3_common

Common point of potential free alarm 3

2

Dig_Out3_n_open

Normally open contact of potential free alarm 3

3

Dig_Out3_n_closed

Normally closed contact of potential free alarm 3

4

Dig_Out4_common

Common point of potential free alarm 4

5

Dig_Out4_n_open

Normally open contact of potential free alarm 4

6

Dig_Out4_n_closed

Normally closed contact of potential free alarm 4

7

--

DO NOT CONNECT

8

--

Table 1 : Signal connector pin assignments

Signal connections can be brought back to the front of the shelf via the front signal connection card

(Figure 17).

Figure 17 : Front signal connectors

Figure 18 : Sub-D 26 poles pin layout


The following table lists all of the pin assignments for the Sub-D26 signal connector:

X104

Name

Remarks

1

DIG_IN4

External digital input 4 – used with 0V signal

2

DIG_IN3

External digital input 3 – used with 0V signal

3

DIG_IN2

External digital input 2 – used with 0V signal

4

DIG_IN1

External digital input 1 – used with 0V signal

5

--

DO NOT CONNECT

6

Dig_Out4_n_open

Normally open contact of potential free alarm 4

7

Dig_Out3_n_open

Normally open contact of potential free alarm 3

8

Dig_Out2_n_open

Normally open contact of potential free alarm 2

9

Dig_Out1_n_open

Normally open contact of potential free alarm 1

10

0 V signal

0V signal

11

0 V signal

12

0 V signal

13

0 V signal

14

--

DO NOT CONNECT

15

Dig_Out4_common

Common point of potential free alarm 4

16

Dig_Out3_common

Common point of potential free alarm 3

Advertising