3 54 vdc bus voltage, 54 vdc bus voltage – Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 35

Advertising
background image

0300072-J0 RevA

Page 31 of 46

Min. Current for Discharge Alarm

-2 Amps

x

Boost Automatic

False

x

Boost Activation Low Voltage

46.0 Vdc

x

Boost Termination Voltage

56.4 Vdc

x

When reached ; back to Float

Boost Termination Current

2 Amps

x

When reached ; back to Float

Boost Termination Time

120 minutes

x

When reached ; back to Float

Battery Test (BT) End Voltage

46.0Vdc

x

BT Discharge Ratio

0%

x

Editable with Battery licence

BT Interval

0 day

x

No automatic test, manual start only

BT Discharge Current

1000 Amps

x

BT Min. Discharge Current

2 Amps

x

BT Time Out

10 minutes

x

Digital input 1 Name

Digital input 1

x

Digital input 2 Name

Digital input 2

x

Digital input 3 Name

Digital input 3

x

Digital input 4 Name

Digital input 4

x

Read Access Users

1, 2, 3, 4, 5

x

Write Access Users

0

x

Table 5 : Overview factory settings MCU

4.3.3 54 Vdc Bus Voltage

The float voltage at +25°C can be adjusted. In the edit mode, go to the DC System tab and click on

“Configuration”. Figure 28 below shows the Bus voltage screen through which setting changes can be made by

entering a new value and clicking on “Modify”. It is important to note that these values will be used as references

for alarms.