4 battery setup, Battery setup – Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 36

Advertising
background image

0300072-J0 RevA

Page 32 of 46

Figure 28: Bs voltage

4.3.4 Battery Setup

The battery and related alarms can be configured individually.
Temperature compensation

The bus voltage (and hence the battery charging voltage) can be automatically adjusted proportionate to the

ambient temperature around the batteries.
The value of this compensation is given by the battery manufacturer. Note that the compensation is usually

given per 2V cell. As the DC Bus is 48Vdc, this value must be multiplied by 24 to obtain the figure to be set in

the dedicated field of the Comp@s menu (see Figure 29 below).

Figure 29 : Temperature compensation

Battery String Capacity

The “Battery String Capacity” is the Ah value of the installed battery blocks (see Figure 30).

NOTE:

You should not install a battery with a capacity greater than

62Ah. Therefore the “battery string

capacity” is limited to 62Ah.

Battery Charge Current Limit

The maximum charging current is defined by the user. Usually the maximum charging current in Amps is one

tenth of the battery capacity in Ah. Refer to the specifications of the battery and the recommendations given by

the battery manufacturer.

NOTE:

The maximum battery current is calculated as the difference between the available rectifier

current (up to 7 Amps per rectifier at 43Vdc) and the load current.

The “Battery Charge Current” limit is factory pre-set to 1000 Amps. This means the batteries

are not subject to a current limitation. The maximum charging current can be automatically

limited by changing the setting in Comp@s.

Battery Temperature

The same sensor is used both to monitor battery temperature and to provide the temperature compensation

reference. The battery temperature function is always active and a battery alarm is given by the MCU LED and

the corresponding relay. An alarm is generated when the battery temperature reaches one of the trip levels (low

or high limit). A “Battery Temperature Sensor Fail” alarm is indicated when the temperature sensor is out of

range: i.e. open circuit, not connected or in short circuit.

Advertising