1 switching on and off, 1 switching on, 2 switching off – Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 32: 2 rectifiers 300 w: cxrf 48-300w, Switching on and off, Switching on, Switching off, Rectifiers 300 w: cxrf 48-300w

Advertising
background image

0300072-J0 RevA

Page 28 of 46

LED

4

OPERATING THE 48-300W MODULAR SWITCHED

MODE RECTIFIER SYSTEM

4.1 Switching ON and OFF

4.1.1 Switching ON

After powering up the 48-300W Modular Switched Mode Rectifier System, please verify that the following:

The mains is ON.

The rectifiers correctly report mains present. (Green LEDs on each rectifier should illuminate).

If the system is fitted with a Comp@s board, after 30 seconds the leftmost LED should be permanently

ON

Note: LED continues to flash if no Comp@s is present. If it is present, verify the display: V =~54.0 V

Close the breaker for the battery (if present).

The system is then operational. Some alarms may be ON, depending of the settings on the MCU.

4.1.2 Switching OFF

In order to switch off the complete system, use the external mains disconnect device. If the shelf has a battery

back-up, pull the battery breaker button (the LVD will open) too.

NOTE:

The mains disconnect device and the battery breaker must always be easily accessible to

facilitate system shut down in an emergency. In this case, the battery is disconnected from the

system as the LVD is open and the load is no longer supplied by the DC Bus.

4.2 Rectifiers 300 W: CXRF 48-300W

There is an LED on the rectifier front panel which illuminates in green, orange or red depending upon the status

of that unit. When in fault condition, the rectifier sends an alarm signal and the LED flashes. This signal is

detected by the MCU.

Figure 27 : CXRF 48-300W

Advertising