Figure 34 below illustrates some alarm and relay associations:

Figure 34: Alarms

4.4.3 Battery Test

Depending on the Comp@s license procured with the system, there are two different battery tests.

4.4.3.1 B

ATTERY

C

ONTINUITY

C

HECK

This check is part of the Basic License. When the test is manually started, the output of all installed rectifiers is

set to deliver a low output voltage (lower than the battery voltage). The batteries are discharged by the load

current. All settings are fixed and cannot be changed. The test time and the end test voltage are fixed at 10

minutes and 46Vdc but the battery current is determined by the load. The table below lists all the actions for

conducting this type of battery test:

Status

Conditions

Actions

Comments

Indications

Start

Continuity Test

Battery Test

pressed >10”

Manual start

Stop

Continuity Test

End voltage

reached

Automatic

Test time of 10 minutes

not reached

Battery Alarm

Test time

reached

Automatic

No Alarm

Manual

Battery Test pressed >5”

No Alarm

Reset Alarm

Manual

Perform a short Battery

Test and cancel it

Table 9: Battery Continuity Test