Alpha Technologies Cordex CXCRF 48-300W User Manual
Page 44
0300072-J0 RevA
Page 40 of 46
Figure 35: Comp@s - Battery test
Table 10 lists the actions for conducting a battery test:
Status
Conditions
Actions
Comment
Indication
Start Battery
Test
Test Time
Interval reached
Automatic test when
Battery Test Interval > 0
days
Status MCU
flashing (1Hz)
during test
Battery test
button pressed
more than 5sec.
Manual start
Status MCU
flashing (1Hz)
during test
Manual test
started from
Comp@s
(Control tab)
Start (Force) Battery Test
Status MCU
flashing (1Hz)
during test
Stop Battery
Test
Discharge
power limit
reached
Automatic
End Voltage AND Battery
Test Time Out are not
reached
No Alarm
End voltage
reached
Automatic
Preset Discharge power
not reached
Battery Alarm
Test Time
Out reached
Automatic
Preset Discharge Ratio
not reached
Battery Alarm
Manual
Batt. Test button pressed
more than 5 sec.
No Alarm
Via Comp@s
Back to Float
No Alarm
Reset Alarm
Manual
Perform a short Battery
Test
Via Comp@s
Reset Last Battery Test
State
Table 10: Battery test