Page 40 of 46

Figure 35: Comp@s - Battery test

Table 10 lists the actions for conducting a battery test:

Status

Conditions

Actions

Comment

Indication

Start Battery

Test

Test Time

Interval reached

Automatic test when

Battery Test Interval > 0

days

Status MCU

flashing (1Hz)

during test

Battery test

button pressed

more than 5sec.

Manual start

Status MCU

flashing (1Hz)

during test

Manual test

started from

Comp@s

(Control tab)

Start (Force) Battery Test

Status MCU

flashing (1Hz)

during test

Stop Battery

Test

Discharge

power limit

reached

Automatic

End Voltage AND Battery

Test Time Out are not

reached

No Alarm

End voltage

reached

Automatic

Preset Discharge power

not reached

Battery Alarm

Test Time

Out reached

Automatic

Preset Discharge Ratio

not reached

Battery Alarm

Manual

Batt. Test button pressed

more than 5 sec.

No Alarm

Via Comp@s

Back to Float

No Alarm

Reset Alarm

Manual

Perform a short Battery

Test

Via Comp@s

Reset Last Battery Test

State

Table 10: Battery test