Figure 20 ), Figure 21 ), N figure 20 – Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 27

Advertising
background image

0300072-J0 RevA

Page 23 of 46

Figure 20 : Rear DC bus connector

DC Bus

+

-

3. Auxiliary DC output:

Each rectifier has a front panel mounted DC output. The polarity is indicated on the front plate.

Insert the wires in the mating connector and secure them by tightening the screws located on top of

the connector. The mating connector can be ordered from Alpha Technologies.

Figure 21 : Front Auxiliary DC output

Auxiliary Output

GND

+

-


NOTE:

On delivery, the “+” pole of the DC bus is FLOATING (i.e. NOT connected to earth). In order to

comply with the SELV (Safety Extra Low Voltage) rules, the “+” DC bus must be connected to

earth.