4.3.2 Factory Preset Settings Overview

Table 5 lists all the default settings of the MCU.

Table

Item

Value

Licence

Comment

1 2 3

General

URL address

192.168.45.2

x

User (as administrator )

admin

x

Case sensitive

Password

compas

x

Case sensitive

Config.Table DC Bus Float

54.0 Vdc

x

At +25°C ; 2.25 Vdc/cell

DC Bus Voltage Extra Low

45.0 Vdc

x

1.88Vdc/ cell

DC Bus Voltage Low

48.0 Vdc

x

2.00Vdc/cell

DC Bus Voltage High

56.5 Vdc

x

2.35Vdc/cell

DC Bus Voltage Extra High

58.0 Vdc

x

2.42Vdc/cell

LVD Disconnect Voltage

43.2 Vdc

x

1.80Vdc/cell

LVD Disconnect Delay

0

x

Temp. Comp. slope

-72 mVdc

x

Only applied when system is in float -3

mVdc/K/cell

Minimum nr. of Present Rectifiers

0

x

Battery Charge Current Limit

/

x

No battery charging current limitation

Battery String Capacity

62 Ah

x

Bat. Temp. Low

0°C

x

Bat. Temp. High

+40°C

x