Battery pre-alarms

Alarms are generated when the DC Bus voltage reaches one of the pre-set alarm levels. In this case, no action

is initiated other than an alarm (major, minor or battery) being generated on the MCU LEDs and the

corresponding relay.

4.3.5 LVD Trip Level

During a battery discharge the internal LVD opens when the battery low voltage trip level is reached. The factory

settings for this are the following:

Description

MCU settings

Comments

Factory setting trip level

43.2Vdc

LVD opens when the value is reached after

the time given in seconds

Factory setting delay

0 second

LVD when MCU removed

CLOSED

opens at typ. 42Vdc

Table 6: LVD Trip level

NOTE:

When the MCU is removed from the shelf (e.g. for adjustment or replacement), the LVD

remains CLOSED and when the mains is absent (shelf working on the battery) the LVD will

open at approximately 42 V. The LVD will re-close automatically when the mains is restored.

4.3.6 Rectifier Settings

It is recommended that the minimum quantity of rectifiers needed in the system is defined in the MCU in order to

generate an alarm, if one or more rectifiers are missing.
Select the Edit Mode and go to the configuration tab of the DC System, change the number of rectifiers, click on

“Modify” and save the new settings. The default setting is “0”.