Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 24

Advertising
background image

0300072-J0 RevA

Page 20 of 46

Signals

If used, make the Ethernet connection via the port on the front of the controller (Figure 14) and signal connectors

at the rear of the shelf (Figure 15)

Figure 14 : Front ethernet port

Figure 15 : Rear signal connectors


Optionally, a set of mating connectors can be provided with the system.

Figure 16 : Signal connector pinning

The following table lists all the pin assignments for the signal connectors:

X110

Name

Remarks

1

--

DO NOT CONNECT

2

--

3

0 V signal

0V signal for Temp. sensor and the four digital inputs

4

Tenv. sensor

Thermal sensor (NTC 10kΩ) with 0V signal

5

DIG_IN1

External digital input 1 – used with 0V signal

6

DIG_IN2

External digital input 2 – used with 0V signal

7

CANH

CAN bus

8

CANL

X111

Name

Remarks

1

DIG_IN3

External digital input 3 – used with 0V signal

2

DIG_IN4

External digital input 4 – used with 0V signal

3

Dig_Out1_common

Common point of potential free alarm 1

4

Dig_Out1_n_open

Normally open contact of potential free alarm 1

5

Dig_Out1_n_closed

Normally closed contact of potential free alarm 1

6

Dig_Out2_common

Common point of potential free alarm 2

7

Dig_Out2_n_open

Normally open contact of potential free alarm 2

Advertising