3.3 DC Inter-bay Copper

The inter-bay bus bar is available in 2500 A
nominal sizing. All inter-bay bus work is contained
within the system racks.

Hot Bay Expansion

An additional bay can be added to the system
while online without shutting down the DC plant.
Review Section "1. Safety" on page 7 before under-
taking this procedure.

3.3.1 DC Return Bus Bar

Each power system bay has two vertical distribu-
tion buses sized to carry the required current (see
Figure 2):

The DC inter-bay return bar runs horizontally
across the back of the rectifier shelves intercon-
necting the vertical return distribution buses in
each bay. The return bus bar is the termination
point for load returns, battery returns, rectifier
positive, and site reference ground.

3.3.2 -48 V Bus Bar

The -48 Vdc inter-bay bar also runs horizontally
across the back of the rectifier shelves intercon-
necting the vertical -48 Vdc distribution buses in
each bay.

)LJXUH ² ,QWHUED\'&FRQQHFWLRQV UHDUYLHZ

5HWXUQ

5HWXUQ

9

9

3.4 Battery

Terminations

There are 6 battery termination points (1/2" on 1 3/4" centers and 3/8" on 1" centers) per polarity on each power
system bay (12 termination points if connections are made both front and back).

5HWXUQ

9

)LJXUH ² %DWWHU\WHUPLQDWLRQ UHDUYLHZ