5 distribution shunts – Alpha Technologies Cordex CXPS-D 48-2500_5000A User Manual

Page 19

Advertising
background image



-5HY%

3.5 Distribution

Shunts

Each TPL fuse or breaker bank can be connected to the distribution bus through an optional 800 A / 25 mV
shunt. See Figure 8 and Figure 9.

The individual shunt currents can be viewed on the CXC to monitor load/ battery balance. If the system has more
than four shunts, then installation of the shunt multiplexer panel option is required to increase the number of
observable shunt currents at the CXC to 16. Shunts and TPL fuses may be used for battery protection (program-
ming required).

3.5.1 Shunt Multiplexer Panel

The Cordex controller can monitor up to four current input channels, such as load currents and battery charge
currents. When the number of current inputs is more than four, an optional shunt multiplexer panel monitors the
individual branch load currents within the distribution modules of the individual bay and sends the current mea-
surements to the CXC for data logging and display.

)LJXUH ² 73/VKXQWV

)LJXUH ² %UHDNHUEDQNVKXQW RQHSHUEDQN

)LJXUH ² 6KXQWPX[SDQHOPRXQWHGRQWKHLQVLGHGRRURIWKHWRSGLVWULEXWLRQPRGXOH