6 low voltage load disconnect – Alpha Technologies Cordex CXPS-D 48-2500_5000A User Manual

Page 20

Advertising
background image

-5HY%



3.6 Low Voltage Load Disconnect

The Low Voltage Load Disconnect (LVLD or LVD) feature controls a
high capacity contactor that disconnects the load during extremely
low voltage conditions. The system loads are automatically recon-
nected once AC is restored and battery voltage has risen above a
preset value.

The parameters for LVD activation and control are set in the

Controls

> Configure Controls

menu in the CXC controller. Refer to the section

titled "Controls" in the controller software manual.

Each TPL fuse circuit in a given distribution bay, can have its own
LVD. Figure 11 shows the LVDs in a distribution module with two
banks of TPL fuses.

An LVD is also an option for a bank of breakers in a distribution
module.

LVDs can also be configured as Low Voltage Battery Disconnects
(LVBD).

LVD Override

Activation of all LVDs, by the controller, is through Relay 1 (LVD 1).

To manually override the LVDs, position the LVD Override switch to
OVERRIDE. This switch is mounted inside the door of the distribution
module with the controller—see Figure 12.

)LJXUH ² /9'FLUFXLWV

127(

6HWWLQJWKH/9'2YHUULGHVZLWFKWR29(55,'(JHQHUDWHVDQDODUPRQWKH&;&6HHWKH
'LJLWDO$ODUPVVHFWLRQXQGHU&RQ¿JXUH$ODUPVLQWKHFRQWUROOHUVRIWZDUHPDQXDO

Advertising
This manual is related to the following products: