Water Temperature Requirement 
and Hydronic Refrigeration
Chilled Water Temperature
Modules are designed for a leaving water temperature 
range from 40°F to 62°F. All cataloged modules can operate 
safely in this range without the need of special controls or 
glycol additives. Leaving water temperatures below 40°F 
can result in evaporator suction temperatures below the 
freezing point of water. Therefore, a glycol solution additive 
is required that will protect the evaporator from freeze ups 
at lower operating suction temperatures. The full range of 
leaving chiller fl uid using glycol is 20°F to 62°F.
Hydronic Refrigeration
Figure 1 - Chilled Water Circuit
Note: Figure 1 depicts Hydronic piping in each ClimaCool chiller module and is shown with water isolation valves.
Service Ports (3/4”)
Isolation Ball Valves
(2 or 2-1/2”)
Pete’s Ports
Heat Exchanger
Leaving Chilled Water
Temperature Sensor
Refrigerant Circuit #1
Refrigerant Circuit #2