Refrigerant charging procedure – ClimaCool UCR 30, 50 and 70 tons Manual User Manual
Page 54
 
www.climacoolcorp.com
54
Refrigerant Charging Procedure
Refrigerant Charging
Once leak testing and evacuation are complete, refrigerant 
charging may commence. Always refer to the unit 
nameplate and guidelines within this section in order to 
establish the quantity of refrigerant required. IMPORTANT: 
Always introduce refrigerant into a system using a charging 
manifold with gauges, along with a refrigerant scale to 
accurately weigh the refrigerant cylinder throughout the 
entire charging process. As noted in an earlier section, the 
end user and installing contractor must provide and fi eld 
charge refrigerant R-410A.
CAUTION: Never dispense refrigerant amounts into the 
receiver which may exceed its liquid holding capacity. The 
refrigeration system in our model UCR 030 is equipped 
with 72 pound receivers (at 80% full). Both refrigeration 
systems in models UCR050 and UCR070 are equipped with 
84 pound receivers (at 80% full).
As much refrigerant as possible should be charged in this 
manner until the receiver holding capacity is achieved, or 
system pressures equalize preventing additional refrigerant 
from being added. Even if system equalization occurs, it is 
still possible to inject liquid refrigerant into the system by 
placing the refrigerant cylinder into a luke warm water bath. 
NO WARMER THAN 110°F.
SAFETY ALERT: Cylinder pressures must be closely 
monitored whenever a refrigerant cylinder is being heated 
in ANY manner. Allowing pressures to exceed those for 
which the cylinder is rated, may result in cylinder rupturing, 
personal injury and/or property damage or even death. 
Once system and refrigerant cylinder tank pressures have 
equalized, it will be necessary to fi nish the refrigerant 
charging process by gradually metering small bursts of liquid 
refrigerant into the suction line of the compressor while it is 
operating. 
SAFETY ALERT: Never attempt to vapor charge into 
the system high side, whether the compressor is ON 
or OFF. This may result in refrigerant fl owing from the 
refrigeration system into the charging cylinder. Cylinders 
can quickly be over pressurized causing them to rupture 
with resultant injury and property damage. 
IMPORTANT: Never dispense liquid refrigerant into the 
suction port of a compressor while it is not running. 
If adding additional refrigerant is necessary, you must 
gradually meter liquid refrigerant into the suction port 
of the compressor ONLY WHILE THE COMPRESSOR IS 
RUNNING, and only through a metering valve.
The only exception to the above recommendations to meter 
in liquid refrigerant into the suction line is the following: 
Providing the ENTIRE contents of the refrigerant cylinder 
is intended to be added to a refrigeration system, it is 
perfectly acceptable to vapor charge from this cylinder into 
the compressor suction line until all refrigerant is injected.
The amount of refrigerant required in a system depends on 
the following:
•
Model size of the equipment.
•
The distance of the interconnecting lines between the 
UCR module and the condenser section.
•
The specifi c head pressure control methods used for 
low ambient operation.
•
What (if any) fan cycling controls are supplied with the 
condenser.
•
Whether optional compressor unloading is possible 
using hot gas bypass.
Refer to Tables 1 and 2 to determine the total amount of 
additional refrigerant at initial startup which accommodates 
all dependant variables listed above. Although the charge 
in the table refers to a winter charge, it is suitable for both 
winter and summer operation.