Startup – ClimaCool UCR 30, 50 and 70 tons Manual User Manual
Page 40
 
www.climacoolcorp.com
40
Startup
All startups must be performed by ClimaCool factory 
trained personnel.
1.
Built into the logic of the CoolLogic Control System 
is an anti-short cycle timer which will prevent the 
compressors from re-starting immediately following a 
compressor shutdown.
2.
If the chilled water temperature is above the normal 
operating level (greater than 90°F), all load should be 
removed from the chilled water system and the suction 
temperature should be monitored to prevent high 
current draw. 
3.
When all temperatures are within operating limits, all 
high and low pressure safety switches should be tested 
for each refrigeration system.
4.
Once stable conditions have been achieved, the 
refrigeration system’s high and low pressures, 
compressor amp draw, voltage input level, and water 
system temperatures and pressures should be logged 
for each chiller module separately. 
5.
Check that oil level is between 1/3 and 1/2 of the sight 
glass. (See page 50– Oil Levels).
6.
The action of the controller should be checked for 
correct operation and control.
7.
Extract three water samples from the evaporator 
water system using bottles provided from the Water 
Sample test kit. Confi rm that the sample bottles 
are fi lled to the top leaving no air in the bottles. All 
three sample bottles must have labels fi lled out per 
instruction included with the bottles. Ship the bottles 
immediately to the appropriate water testing laboratory 
as per the instructions included with the bottles.
Adjusting Unit Charge and TXV’s Using Superheat 
and Subcooling Method
Due to varying installation conditions/applications and to 
optimize performance, proper refrigerant charge and TXV 
adjustment must be confi rmed. 
After checking compressor rotation, choose a circuit to be 
tested fi rst. Connect test equipment to monitor the suction 
Line and Liquid Line temperatures simultaneously. Place a 
manifold gauge set on the suction line and liquid line. Start 
the compressor. As long as the suction pressure is high 
enough to prevent the low pressure switch from tripping, 
run compressor for fi ve minutes. 
Verify proper superheat by subtracting the saturated 
evaporative temperature from the suction line temperature. 
The saturated evaporative temperature is found by 
converting the suction pressure reading on the manifold 
gauge, to the related temperature. Proper superheat 
temperature range is 6-12°F. If superheat is low, this may 
indicate that TXV is overfeeding. To adjust the TXV, turn the 
adjustment stem clockwise. This will cause the superheat 
to rise. Wait fi ve minutes before checking results of 
adjustment. Repeat until desired superheat is achieved.
After verifying proper superheat, then verify proper 
subcooling. This is accomplished by subtracting liquid line 
temperature from the saturated condensing temperature. 
Saturated condensing temperature is found by converting 
the liquid line pressure reading on the manifold gauge, to 
the related temperature. Normal subcooling temperature 
range, at the condenser, is 5 – 15°F, BUT for total accuracy 
please follow the charge recommendations found in the 
selection program. If subcooling is too low, then refrigerant 
must be added to the system. Add charge and wait fi ve 
minutes before checking results. If subcooling is too high, 
then refrigerant must be removed from the system.