Water Treatment
Water quality is of the utmost importance for the proper 
care and maintenance of the modular chiller system. 
Proper water treatment is a specialized industry and we 
recommend consulting an expert in this fi eld to analyze the 
water for compliance with the water quality parameters 
listed in Table 1. The material used in the ClimaCool chiller 
exposed to the water are type 316 stainless steel, pure 
copper, and carbon steel. Other materials may exist external 
to the ClimaCool chiller. It is the user’s responsibility to 
ensure these materials are compatible with the treated 
water. Regular treatment of the water will increase 
longevity of your system. Failure to provide adequate 
fi ltration or treatment of evaporator water will void the 
ClimaCool module’s warranty.
Heavy-Contaminated Water
In such instances whereby the particulates in the water are 
excessive it is recommended to install an intermediate plate 
& frame heat exchanger to isolate the ClimaCool chiller from 
the building water system. 
*(<;065
t &YDFTTJWF$IMPSJOF 6OEJTTPMWFE4PMJETBOE
PUIFSJNQSPQFSXBUFSRVBMJUZDPOEJUJPOT
WILL DAMAGEUIFJOUFSOBMIFBUFYDIBOHFSBOE
WILL VOID YOUR WARRANTY!
Table 1 - Water Quality Parameters
WATERCONTAINING
CONCENTRATION
Ammonia
Lessthan2.0mg/l
CaCO3Alkalinity
30Ͳ500mg/l
CaCO3Hardness
30Ͳ500mg/l
Chlorides
Lessthan200mg/l
DissolvedSolids
Lessthan1000mg/l
Iron
Lessthan5.0mg/l
Manganese
Lessthan0.4mg/l
Nitrate
Lessthan100mg/l
pH
7.0Ͳ9.0
Sulphate
LessThan200mg/l