Split system interconnecting piping – ClimaCool UCR 30, 50 and 70 tons Manual User Manual
Page 53
 
53
www.climacoolcorp.com
Split System Interconnecting Piping
Discharge Line Piping Recommendations
All discharge lines should be kept as short as possible and the 
line sizing is determined to provide for a low-pressure drop. 
There should always be a gradual negative elevation change 
when traversing from the remote condenser location to the 
UCR module section. Avoid any reversing elevation changes 
throughout this discharge line run. Horizontal liquid lines 
should be sloped downward, in the direction of refrigerant 
fl ow, at a pitch of 1/8” per foot. The total equivalent distance 
between the condenser and the UCR section (including 
allowances for U-bends and 90° elbows) should not exceed 
100 feet. Vertical discharge lines greater than 5 feet required 
a P- trap at the base of the riser as well as an inverted trap 
at the top of the discharge line run (See Remote Condenser 
Installation Guidelines – page 29).The inverted trap should 
be the highest point in the discharge line. Additional P-traps 
should be added at every 10 feet of additional vertical rise in 
the discharge line. The maximum vertical distance between 
the lower UCR module section and the higher remote 
condenser location should be less than 50 feet. UCR modules 
equipped with optional compressor unloading by means of 
hot gas bypass require the use of double risers for vertical 
discharge line runs (See Remote Condenser Installation 
Guidelines – page 29).
Remote Condenser Piping Connections
The discharge and liquid line connections at the remote 
condenser section are equipped with capped, stub-out tubes. 
It is mandatory that isolation ball valves and check valves 
are fi eld installed at both the inlet and outlet connections 
locations of each remote condenser. These ball valves and 
check valves are shipped loose with every ClimaCool UCR 
split systems chiller package. Refer to Remote Condenser 
Installation Guidelines – page 29 for schematic representation 
of the isolation and check valve functions.
Leak Testing – Refrigeration Side
Prior to startup, the entire system should be leak tested using 
electronic leak detection. Carefully leak test both factory and 
fi eld made joints including condenser coils. Although each 
unit is factory leak tested, joints do loosen and sometimes 
break during shipment.
Refrigeration System Reprocessing
Once a refrigeration system has been exposed to atmosphere 
for any length of time (several minutes to an hour), it is 
imperative that the system undergo a thorough evacuation to 
remove moisture and non-condensibles. With split systems, 
provisions should be made to evacuate the interconnecting 
discharge and liquid lines prior to opening the shutoff valves 
provided in each section. Non-condensibles (air, nitrogen 
trace gases, etc.) trapped in the systems will elevate 
condensing pressures. This will result in ineffi
cient system
operation and potentially cause nuisance head pressure 
trips. Moisture in the system can cause chemical reactions 
with many POE oil additives resulting in the formation of 
undesirable acids which corrode the system.
IMPORTANT: NEVER start the compressors while in a 
vacuum. Serious damage can occur to the motor windings 
in this condition. Only use a vacuum pump of known reliable 
operation, specifi cally, one that can achieve a vacuum level 
of 100-200 microns with the pump service port closed. Prior 
to evacuation, make sure all refrigerant isolation valves 
are OPEN and that the main liquid line solenoid valves are 
energized (apply 24VAC to the solenoids coils using a 75VA 
transformer or equivalent). Alternatively, you may choose 
to manifold multiple evacuation hoses together and connect 
vacuum lines to refrigeration access fi ttings on both sides of 
the liquid line solenoid valves. Ensure that the vacuum pump 
is connected to both high and low sides of the system with 
copper tube or vacuum hoses. A vacuum gauge capable of 
reading vacuum levels in microns (with readability as low as 
100 microns) must be connected to the system, preferably 
close to the compressor module. Ordinary gauges from a 
standard charging manifold are unacceptable! 
Operate the vacuum pump until a vacuum level below 500 
microns is achieved. Close the vacuum pump service valves to 
isolate the pump from the refrigeration system. This initiates 
a “vacuum decay test” by monitoring 
system pressure rise for a time period of 15 minutes. The 
refrigeration system vacuum gauge should not rise more 
than 200 microns within this 15 minute period. Pressures 
that rise beyond this decay criteria indicate the existence 
of a leak, or more likely, indicate the presence of moisture 
or non-condensable in the system. If a leak is suspected, it 
must be identifi ed and corrected before proceeding with 
the evacuation. If moisture contamination is the suspected 
problem, rapid evacuation processes may serve only to freeze 
the moisture inside the system, allowing only for the slow 
process of sublimation to remove all of the water. Then it is 
recommended to apply heat lamps to the compressor and 
receiver to elevate the temperature inside the system above 
the freezing point while evacuating. Successive dry nitrogen 
fi lls and purges can prove equally benefi cial in removing 
excessive moisture from a system.
WARNING
To avoid the release of refrigerant into the atmosphere, 
the refrigerant circuit of this unit must be serviced only by 
technicians who meet local, state and federal profi ciency 
requirements.
All refrigerant discharged from this unit must be recovered 
WITHOUT EXCEPTION. Technicians must follow industry 
accepted guidelines and all local, state and federal statutes for 
the recovery and disposal of refrigerants.
If a compressor is removed from this unit, system refrigerant 
circuit oil will remain in the compressor. To avoid leakage of 
compressor oil, the refrigerant lines of the compressor must 
be sealed after it is removed.