Filling the water system – ClimaCool UCR 30, 50 and 70 tons Manual User Manual
Page 17
 
17
www.climacoolcorp.com
Filling the Water System
It is imperative that the water systems are free from debris 
prior to initial operation. See page 18– Water Treatment for a 
comprehensive list of precautions.
Filling, Purging and Leak Testing the System
After the water system has been properly installed a visual 
inspection should be made to all joints for tightness. If the chiller 
is to be installed in an existing system, the cleanliness of the 
existing system can be judged from the operating conditions of 
the present machines. The cooling tower in particular, should be 
inspected and cleaned if required. It is a good practice to at least 
fl ush the existing system and ideally, to acid wash the system 
before connecting a new chiller.
We recommend the following sequence to fi ll and leak check 
the water system for modules WITHOUT Water Isolation Valves:
1.
Ensure that all drain valves are closed and that all main 
water header isolation valves are opened.
2.
All modules are equipped with 3/4” fi ll and fl ush valves with 
lines teed into the inlet and outlet connections into and out 
the heat exchanger. Ensure these 3/4” valves are CLOSED.
3.
The system should be fi lled with clean water sent through a 
strainer and the system checked for leaks.
4.
Once the main water lines and the chiller headers are fi lled 
with clean water, purge and repeat the fi lling process 
several times.
5.
Following the fi nal fi lling and leak checking procedure, air 
should be purged from the system. 
We recommend the following sequence to fi ll and leak check 
the water system for modules WITH Water Isolation Valves:
1.
Close all water isolation valves inside each module which 
isolate the individual heat exchanger.
2.
Ensure that all drain valves are closed and that all water 
main isolation valves are opened.
3.
The system should be fi lled with clean water sent through a 
strainer and the system checked for leaks.
4.
Once the main water lines and the chiller headers are fi lled 
with clean water, purge and repeat the fi lling process 
several times.
5.
All modules are equipped with 3/4” fi ll and fl ush valves with 
lines teed into the inlet and outlet connections into and out 
the heat exchanger. Ensure these 3/4” valves are CLOSED.
6.
Open the water isolation valves inside each modular chiller 
and repeat the fi lling process, this time also checking for 
leaks inside each module.
7.
Following the fi nal fi lling and leak checking procedure, air 
should be purged from the system. 
Cleaning the System
We recommend the following sequence to properly clean the 
water systems:
1.
Whenever possible, install a temporary bypass line between 
the main supply and return water header of the chilled water 
system prior to cleaning the system. Open the main header 
bypass lines to divert the initial water fl ow around the module 
heat exchanger until you are confi dent the circulating water is 
mostly pure.
2.
Provided the main header bypass lines are installed, close 
all water isolation valves inside all modular chillers equipped 
with manual or automatic water isolation valves. If the 
modules are NOT equipped with water isolation valves, we 
recommend installing 3-way main header bypass valves so 
the initial water fl ow bypasses all module heat exchangers.
3.
The pumps should be run with the strainer in place (see 
Starting the Pumps section for proper pump startup). All 
external hydronic branches should be open to all devices in 
the system. 
4.
After several hours of operation, the strainer should be 
isolated and cleaned. 
5.
Step 4 should be repeated until there is no more debris being 
collected by the strainer.
6.
Open all water isolation valves inside each module equipped 
with manual or automatic water isolation valves (see step 
7 for modules NOT equipped with water valves). If bypass 
lines are not installed as described in step 1 above, it is 
recommended to drain out the initial fi ll of water to help fl ush 
out debris. Finally, close off the main header bypass lines 
referred to in step 1 above, and open the fl ow to the main 
water headers. Repeat steps 3, 4 and 5 until there is no more 
debris being collected by the strainer.
7.
If bypass lines are not installed as described in step 1 above, 
and if the modules are NOT equipped with water isolation 
valves, it is recommended to drain out the initial fi ll of water 
to help fl ush out debris. Before refi lling and purging the 
system again the strainers should be removed and cleaned. 
Repeat steps 3, 4 and 5 until there is no more debris being 
collected by the strainer. 
Starting the Pumps
Follow manufacturer’s recommendations when starting the 
pumps for the fi rst time. The system should be checked for leaks 
and air purged with the pumps in operation. The pressure drop 
across the heat exchangers will give a good indication of fl ow 
through the system (See page 19-20 – Evaporator Water Pressure 
Drop Charts). This should be immediately checked against the 
expected pressure drop for the fl ow rate required. If the pressure 
drop begins to fall and the fl ow rate is falling, this could indicate 
the need to clean the strainers.