Split system startup, Attention installer, Compressor precautions – ClimaCool UCR 30, 50 and 70 tons Manual User Manual
Page 42
 
www.climacoolcorp.com
42
Split System Startup
Once installation is complete, check the following:
•
All refrigerant and electrical connections must be tight. 
Tighten all loose wire terminal connections that may 
have loosened in shipping.
•
The compressor oil is at the proper level in the oil sight 
glass for the compressor being used (See page 50 - 
Compressor Information).
•
Check initial settings of thermostats and pressure 
controls. All adjustable pressure controls and valves will 
require a fi nal adjustment with the use of a compatible 
gauge.
•
Check the control panel to be sure that all wiring is in 
accord with the unit wiring diagram.
•
Check all three phase motors for proper rotation.
Compressor Precautions
Care must be taken when initially starting a system or 
when the system has been off for an extended period. At 
this time, the compressor may contain liquid refrigerant. 
Simply starting the system and walking away may result 
in irreparable compressor damage not covered under 
warranty. To prevent compressor damage, one or more of 
the following steps may be used:
Step 1: All compressors are supplied with a crankcase 
heater. It must be activated 24 hours prior to starting the 
compressor. Be sure to check that the heater is functional. 
This can be done by simply touching the compressor in the 
area of the heater. It should feel warm to the touch. This 
check should be performed shortly after energizing the 
heater and again prior to starting the compressor. If the 
compressor is cold, do not attempt to start it. Locate the 
source of the problem, correct it and wait 24 hours before 
starting the compressor.
Step 2: Use a safe heat source such as a heat lamp on the 
compressor crankcase for approximately 1/2 hour before 
startup. Never use a torch or heat gun. They can raise 
system pressures to dangerous levels in a very short time 
resulting in injury to personnel as well as property damage.
Step 3: After following steps 1 and 2 above you can be 
relatively certain that no liquid refrigerant is left in the 
compressor. This does not mean that liquid refrigerant is 
not present elsewhere in the low side. To avoid compressor 
damage on startup, deactivate the liquid solenoid and 
“bump” the compressor, using the controller “POWER” 
switch, several times. The fi rst 2 or 3 times the compressor 
is “bumped” it should not be allowed to run more than 2 
or 3 seconds. Increase the run time to 5, 10 and 15 seconds 
over the next 3 “bumps”. This will rapidly reduce low side 
pressure causing any liquid to boil off quickly. At this point it 
is usually safe to allow the compressor to run.
Step 4: After starting the compressor, listen for unusual 
sounds such as knocking. Should they be heard, immediately 
stop the compressor. Do not restart until the problem is 
resolved. While scroll compressors are more tolerant to 
liquid refrigerant than reciprocating types of compressors, 
the above precautions should still be observed. Rotational 
direction is very important with three phase scroll 
compressors. Running these compressors with reversed 
rotation will result in damage not covered by warranty. 
When starting a three phase scroll compressor, refrigerant 
pressure gauges must be attached to both the high and 
low pressure ports provided on the system. With the 
compressor rotating in the proper direction, system suction 
pressure should drop and discharge pressure should 
rise to appropriate levels within a few seconds after the 
compressor is stated. If this is not the case, the compressor 
is probably running in reversed rotation. Each chiller is 
computer tested and all three phase motors, (pumps and 
compressors) are in proper phase when it leaves the factory. 
Turn the power off at the main disconnect and reverse any 
two of the three main power leads and restart. Observe 
the suction and discharge pressure gauges to verify that 
the compressor is rotating correctly. If pressures are still 
not appropriate, some other problem has developed which 
must be found and corrected prior to running the system.
ATTENTION INSTALLER
3 Phase Scroll Compressor Units
t *GUIJTVOJUVTFTB1IBTF4DSPMM$PNQSFTTPS UIFGPMMPXJOH
JOTUSVDUJPOT
MUST BEGPMMPXFE
6OJUQPXFSTVQQMZ
MUST BEXJSFEJOUIFQSPQFSTFRVFODFUPBWPJE
EBNBHFUPUIF1IBTF4DSPMM$PNQSFTTPS
4DSPMM$PNQSFTTPSTXJUI
INCORRECT SPUBUJPOTIPXUIFGPMMPXJOH
DIBSBDUFSJTUJDT
 )JHITPVOEMFWFM
 )JHITVDUJPOQSFTTVSFBOEMPXEJTDIBHFQSFTTVSF
 -PXDVSSFOUESBX
*GBOZPGUIFUISFFBCPWFDIBSBDUFSJTUJDTFYJTU TXBQUXPPGUIF
UISFFTVQQMZXJSFTBUUIFEJTDPOOFDUBOESFDIFDLDPNQSFTTPSGPS
JODPSSFDUSPUBUJPO