Head pressure control valve operation (lac-10) – ClimaCool UCR 30, 50 and 70 tons Manual User Manual
Page 24
 
www.climacoolcorp.com
24
High and Low Ambient Stability
The design of air conditioning systems, utilizing air cooled 
condensing units, involves two main problems that must be 
solved if the system is to operate reliably and economically 
high ambient and low ambient operation. If the condensing 
unit is properly sized, it will operate satisfactorily during 
extremely high ambient temperatures. However, some units 
will be required to operate at ambient temperatures below 
their design dry bulb temperature during most of the year; 
the solution to low ambient operation is more complex. 
Without good head pressure control during low ambient 
operation, the system can experience both running cycle 
and off -cycle problems. Since the pressure diff erential 
across the thermostatic expansion valve port aff ects the 
rate of refrigerant fl ow, low head pressure generally causes 
insuffi
cient refrigerant to be fed to the evaporator. Failure
to have suffi
cient head pressure will result in low suction
pressure and/or iced evaporator coils. The primary off -
cycle problem is refrigerant migration to the condenser. 
Insuffi
cient fl ow through the TXV will cause a low suction
pressure.
The typical method of maintaining normal head pressure 
in a refrigeration system during periods of low ambient 
temperature is to restrict liquid fl ow from the condenser 
to the receiver, and at the same time divert hot gas to the 
inlet of the receiver. This backs liquid refrigerant up into 
the condenser reducing its capacity which in turn increases 
the condensing pressure. At the same time the hot gas 
raises liquid pressure in the receiver, allowing the system to 
operate normally.
LAC-10 Valve Operation
The valve designation LAC stands for Low Ambient Control. 
The LAC-10 is a three-way modulating valve that responds 
to receiver pressure. As shown in Figure 1, the receiver 
pressure acts under the diaphragm. As the receiver pressure 
drops below the valve setting, the seat moves away from 
the discharge port allowing discharge gas to bypass the 
condenser. This discharge gas warms the liquid in the receiver 
and raises the pressure to the valve setting. At the same time 
discharge gas is bypassing the condenser, liquid fl ow from the 
condenser is restricted, which allows liquid to back up in the 
condenser. Flooding the condenser reduces the area available 
for condensing thus raising the condensing pressure. During 
summer conditions, the seat closes the discharge port due 
to high pressure in the receiver. Therefore, there is full liquid 
fl ow from the condenser to the receiver. 
Refrigerant Migration
During an off cycle there is a potential for refrigerant to 
migrate from the warm receiver to the cold condenser. 
An auxiliary check valve should be used in the liquid line 
between the LAC valves and the receiver to prevent this from 
occurring. See Figure 2. 
Piping Suggestions
The piping schematic shown in Figure 2 is only to illustrate the 
general location of the head pressure control valves in the 
system, refer to the Refrigeration Circuit Diagram (See page 
51) for more information. Note that the schematic shown on 
Figure 2 refl ects the use of two LAC-10 valves required per 
circuit on 50 ton and above models, only one LAC-10 valve is 
required per circuit on 30 ton and below models. 
Head Pressure Control Valve Operation (LAC-10)
Figure 1
Figure 2