Flowline LI90 Commander User Manual

Page 19

Advertising
background image

27 AUG 08

PRELIMINARY MANUAL

19 of 57

Rev 1_3

Commander LI90 Series

Common Information – There are several configuration aspects that are similar for all three
applications in the LI90 series.

• Analog Input

o

The Commander accepts any 4-20 mA signal.

o

The Commander has the ability to accept a 4-20 mA that has been scaled to the
size of the tank / vessel or with a 4-20 mA that is from a non-configured
transmitter (in its original factory setup).

o

There are six parameters required to configure an analog input in the LI90 series.

o

For a scaled output. Use this description when using a transmitter that has been
configured with 4 mA set to an empty tank/vessel and 20 mA set to a full
tank/vessel.

Sensor Max. Range – This is the distance from the bottom of the tank to

the bottom of the installed sensor.

Sensor Dead Band – This is the distance from the full level of liquid to

the bottom of the sensor.

Sensor Height – This is the distance from the bottom of the tank to the

bottom of the installed sensor. This will be the same setting as the Sensor
Max. Range.

Sensor Fill_H – This is the distance from the bottom of the tank to the

highest level of liquid. Adding the Fill_H value to the Dead Band value
will equal the Max. Range or Height values.

Empty Setting – This is the display value when the tank is empty.

Full Setting – This is the display value when the tank is full.