Commander LI90 Series

Rev 1_3

• To change to an Alternation mode, press the DUP soft key and then press

Next.

Alternate Relays #5 and #6

• Enter the LEAD ON relay set point (where

relay #5 will energize) and press Next

• Enter the ALL OFF relay set point (where

both relays will de-energize) and press Next

• Enter the LAG ON relay set point (where

relay #6 will energize) and press Next.

o

You do not need to provide a value for
Relay #6 OFF.

o

Alternate can be used as a Filling or
Emptying configuration.

o

Always make sure that the LAG ON is
the same as the LEAD ON. This will
enable Relays 5 and #6 to alternate
each time a relay is to become
energized.

• To return Relays 5 and 6 back to an independent mode, press the IND soft

key

o

When done, press Exit to leave the Secured Function Section