For a non-scaled output. Use this description when using a transmitter that is
either set with its original Factory Settings or with a transmitter that has a fixed
(non-configurable) 4-20 mA output:

Sensor Max. Range – This is the maximum range of the sensor. This is

typically the 4 mA set point for the sensor. Use the sensor’s manual to
obtain the sensors maximum range (4 mA output).

Sensor Dead Band – This is the dead band for the level sensor. Use the

sensor’s manual to obtain the sensors dead band (20 mA output).

Sensor Height – This is the distance from the bottom of the tank to the

bottom of the installed sensor

Sensor Fill_H – This is the distance from the bottom of the tank to the

highest level of liquid

Empty Setting – This is the display value when the tank is empty.
Full Setting – This is the display value when the tank is full.