Configuration of Outputs

o

Once in the Secured Function Section, press the Config Outputs soft key

o

Each relay will ask for a Relay ON and Relay OFF level. These settings must be
in the same units used for the Empty and Full settings

Relay ON

Relay OFF

• If you are reading between 0 to 500 gallons, then the relay set points must

be in gallons

• For Pumps and Valves, use both settings as the ON/OPEN and

OFF/CLOSE points for the device

• For Alarms, use the ON point where the relay will start and the OFF as a

hysteresis to prevent chattering of the relay

High Alarm

Low Alarm

Automatic Fill

Automatic Empty

o

To change a value, first press the Enter key

• The value will be highlighted

• Use the 10-digit keypad to enter the desired value

• I.e. for 123.4, press the following keys: <F1>,

<F2>,<F3>,<.>,<F4>,

• Press Enter when completed to store this value to memory