Commander LI90 Series

Configuration of Outputs

o

Once in the Secured Function Section, press the Config Outputs soft key

• Relays #1 and #2 will ask for a Relay ON and Relay OFF level. These

settings must be in the same units used for the Empty and Full settings


Relay ON

Relay OFF

• If you are reading between 0 to 500 gallons, then the relay set points

must be in gallons

• For Pumps and Valves, use both settings as the ON/OPEN and

OFF/CLOSE points for the device

• For Alarms, use the ON point where the relay will start and the OFF as

a hysteresis to prevent chattering of the relay

High Alarm

Low Alarm

Automatic Fill

Automatic Empty