Commander LI90 Series

• To use as Independent Relay mode, press the IND soft key and then press

Next.

Independent Relays #5 and #6

• Enter the Relay #5 ON set point (where Relay

#5will energize) and press Next

• Enter the Relay #5 OFF set point (where

Relay #5 will de-energize) and press Next

• Enter the Relay #6 ON set point (where Relay

#6 will energize) and press Next.

• Enter the Relay #6 OFF set point (where

Relay #6 will de-energize) and press Next.

• To change to a Duplex mode, press the DUP soft key and then press Next.

Duplex Relays #5 and #6

• Enter the LEAD ON relay set point (where

the lead relay will energize) and press Next

• Enter the ALL OFF relay set point (where

both relays will de-energize) and press Next

• Enter the LAG ON relay set point (where the

lag relay will energize) and press Next.
o

You do not need to provide a value for
Relay #6 OFF.

o

Duplex can be used as a Filling or
Emptying configuration.

o

Always make sure that the LAG ON is
above the LEAD ON for an Empty
configuration or below the LEAD ON for
a Fill configuration.