Lt81 series upgrade information, Apply power – Fluid Components International GF90_GF92 User Manual

Page 30

Advertising
background image

FLUID COMPONENTS INTERNATIONAL LLC

http://www.fluidcomponents.com

GF Series Flowmeter Models GF90/GF92

26

Doc. No. 06EN003229 Rev. H

Figure 14. Isolated Output Option Wiring Diagram

NOTE:

Follow the wiring diagrams in Appendix A to reconnect the existing flow element to the
replacement GF series flow transmitter, and to install a jumper on the flow element terminal
board if applicable.

The LT analog series flowmeters can be fully upgraded to the GF series flowmeters by replacing the LT
series transmitter with a properly calibrated GF series transmitter. The flow elements are the same except
for wiring differences at the flow element. The analog outputs also change locations. Jumper wire is
added from terminal 2 to terminal 4 of the flow element head terminal block. New connectors will need to
be installed on the transmitter for power, relays, flow element and analog output.

LT81 Series
Upgrade
Information

The input power should not be turned on until the installation has been completed with all connections
verified, power and signal connection board assembly screwed down and the instrument ready to
operate. Be sure any external circuit breakers are on.

Apply