Doc. No. 06EN003229 Rev. H

75

GF Series Flow Meter Models GF90/GF92

FLUID COMPONENTS INTERNATIONAL LLC

http://www.fluidcomponents.com

Example:

4-20 milliampere Output Signal = 1% of 16 milliampere = 0.16 milliampere = Tolerance.

10. Repeat Step 7 for the other flow rates in the Delta R Table for this flowmeter.
11. Compare results of the verification measurements with the output signal values recorded on the

Delta R Data Sheet to determine if the transmitter is functioning properly. Also verify the display
reading matches.

12. Turn power OFF and disconnect the decade resistors. Connect the proper wires from the flow

element to terminal block.

13. Disconnect the milliamp meter. Connect the output load to the appropriate OUT+ and OUT COM

terminals on the lower (I/O/P) board.

14. Close the enclosure, making sure that none of the wires are caught. Ensure that all seals and

gaskets are properly installed. If a custom enclosure exists, be sure it is placed back into safe
operating condition.

If the readings are good, the flow transmitter is good and problem may involve the flow element. If readings
are off, a flow element calibration may be required or the flow transmitter needs to be setup.

NOTE: Any unauthorized repair attempts will void the warranty.

At this time FCI does not consider there to be any field-repairable items with the exception of the replacement
of fuses F1 and F2. Any repair at the component level for either the flow elements and enclosure or the flow
transmitter and attached components is not advised or recommended by FCI.
Contact the authorized FCI field representative (see list of regional territories and the respective agents) or
FCI (see telephone and FAX numbers later in this manual) to determine the best course of action.

Before returning any equipment to FCI, please obtain an RA number for authorization, tracking, and repair/
replacement instructions. If a return is required, remove defective instrument, replace with spare, calibrate,
then return defective instrument to FCI freight prepaid for disposition.

1.

In the event of problems or inquiries regarding the flowmeter, please contact the regional
or country authorized FCI Field Agent. There is an extensive list of these representatives
at the front of this manual.

2.

Before contacting the FCI representative, please be sure that all the applicable
information is near so that a more effective, efficient and timely response may be
provided.

3.

Refer to Appendix D for specific Customer Service policy provisions.

Defective
Parts

Customer
Service

Repair

Advertising