Guidelines for Loop Installation

Table C - Recommended Number of Turns

Perimeter (ft.)

Number of Turns

10

5

20

4

30-40

3

50-100 2

ACCESSORY CONNECTIONS

1. Prevent sharp corners in the geometry of the loop sensor.
2. Install the appropriate number of turns for your loop geometry based on the loop

perimeter. Use Table C (below) as a guide.

3. Use XLP (cross-linked-polyethylene) type of wire. This wire reduces the effects

of moisture and other environmental events in altering the functionality of the
vehicular loop detector.

4. Twist the lead wire at least 6 turns per foot.
5. Use BACKER-ROD to minimize damage to the loop detector wire prior to using the

sealant.

6. Place the loop detector wire and adjust the sensitivity of the vehicular loop

detector unit in a way to minimize the effects of the gate over the loop detector
wire.

!

IMPORTANT!

Some of the following parameters may affect the proper

functionality of the vehicular loop detector.
Consult the manufacturer of the vehicular loop detector and/or loop wire.
• Gate size
• Number of turns in the loop sensor wire
• Distance of the loop sensor wire to the gate at either at the open or close position

Dimension “A” - 5’ for Single Gate

6’ for Dual Gate