TROUBLESHOOTING

LED References

Use the table below to identify the corresponding “TS Ref#” and refer to page 38-41 for
further troubleshooting.

# LED

Status

Meaning

Page 41

TS Ref#(s)

9

“C Loop”

OFF

Normal Condition.

SOLID

Control Board is receiving an input from a device connected to the
C Loop terminal (pages 32, 42).

9, 10

10 “Open”

OFF

Normal Condition.

SOLID

Control board is receiving an input for a device connected to any of
the following input terminals: Exit, Fire, Strike or Open (pages 31, 42).

9, 10

11

“STOP”

OFF

Normal Condition.

SOLID

Control Board is receiving an input from a device connected to the
Stop terminal (pages 31, 42).

9, 10

12 “Close”

OFF

Normal Condition.

SOLID

Control Board is receiving an input from a device connected to the
Close terminal (pages 31, 42).

9, 10

13 “Siren”

OFF

Normal Condition.

SOLID

Second consecutive obstruction has been detected. (page 26).

11, 13, 1, 2

FLASHING

Batteries are critically low.

1, 2

14 “Brake”

OFF

No voltage output on these terminals at the moment.

SOLID

There is 24v DC output on these terminals at the moment.

15 “Diagnose”

OFF

Normal Condition

FLASHING

Errors have been detected; Check LCD Display for messages (page 38-40).

16 “Close Limit”

OFF

Gate is not at the close limit position.

SOLID

Gate is at the close limit position.

FLASHING

Close limit position has been erased or not set (page 20-21).

6

17 “Open Limit”

OFF

Gate is not at the open limit position.

SOLID

Gate is at the open limit position.

FLASHING

Open limit position has been erased or not set (page 20-21).

6

18 “ODS”

OFF

Normal Condition.

SOLID

Obstruction has been detected. (page 26).

11, 13, 1, 2

FLASHING

Overload has been detected. (page 26).

11, 13, 1, 2

19 “Timer”

OFF

The close timer is turned OFF or gate is not at the open limit if the timer is
turned ON. (page 24).

SOLID

Gate is at Open Limit, Timer is turned ON and counting down to close.
(page 24).

FLASHING

Gate is at Open Limit, Timer is turned ON but is not timing out due to a
conflicting command. (page 24).

9, 10

20

“AC VOLTAGE OUTPUT”

SOLID

Normal Condition.

OFF

There is no output voltage from the Modular Power Box.

2

21

“PROTECTION WORKING”

SOLID

Normal Condition.

OFF

EMI Board is damaged and circuit is not protected . Replace EMI Board.

22

“AC VOLTAGE INPUT”

SOLID

Normal Condition.

OFF

Incoming power to Modular Power Box is not sufficient.(page 18).

1

23 “120VAC POWER”

SOLID

Normal Condition for High Voltage installations.

OFF

High Voltage is not supplied to the Modular Power Box (page 18).

1