Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 103

Developed specifically for thermal fluid system use, the Fulton

Combination/Deaerator/Expansion/Thermal Buffer Tank is a patented design. The unique combination of

the operation of these three vessels in one results in numerous advantages including: pipework

simplification, protection of thermal fluid from oxidation, ease of installation, and continuous deaeration of

fluid, avoiding pump cavitation.

Expansion Section:

The expansion section is vital to the thermal fluid system. From ambient to operating temperature, the

thermal fluid in the system will typically expand in the range of 30%, and a vessel capable of handling this

expansion is mandatory. Additional expansion section features include a liquid level switch and manual

fluid levels test connections. In the event of system fluid loss, the level in the expansion section of the

combination tank will drop, and the liquid level switch will shut the unit down. Manual low and high fluid

level test connections are always provided.

Deaerator Section:

At start up the primary purpose of the deaerator section is to remove all volatiles from the system to avoid

pump cavitation. The deaerator section also allows oxygen to be vented from the system on a continuous

basis during operation to avoid oxidation of the thermal fluid, and removes other volatile particles

generated by the fluid itself during system operation.

Thermal Buffer Section: