Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 22

i)

Water Cooling

1. A throttling needle valve should be installed on the inlet side of the water

cooling passages and adjusted so that the outlet water is between

120°F. and 160°F. Typically this means a flow rate of 2-5 GPM at 40°F

inlet temperature. Consult pump manufacturer’s specifications for

dimensions of water cooling connection.

2. The throttling valve on a water cooled pump is designed to automatically

give the proper flow rate for a 40 PSIG or greater supply.

3. If a minimum of 40 PSIG is not available, consult Fulton Thermal

Corporation about resizing the orifice. If the temperature of the cooling

water is greater than 55°F to begin with, a correspondingly greater flow

rate is required.

4. For automatic operation of water cooling, wire a solenoid valve on the

inlet to open whenever the pump motor starter is energized.

5. The outlet flow from the pump must not be restricted in any manner.

Therefore, valves are not to be installed on the outlet. Check local codes

regarding disposal of hot water.