Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 66

Low Inlet Pressure Switch

a) Slowly close the valve on outlet of main circulating pump observing heater inlet pressure

gauge. Note the pressure at which the switch trips. This pressure should be roughly the

set point of the switch minus any differential that is set.

High Outlet Pressure Switch

a) Note the original setting of the switch and turn adjustment screw counterclockwise while

observing heater outlet pressure gauge until switch trips. The pointer on the switch

should be within 2 psi of the observed pressure. Reset switch to the original set point.

Outlet

Inlet

Differential
Pressure Switch