Fulton Vertical Electric (FT-N) Thermal Fluid (hot oil) Heater User Manual

Page 24

Advertising
background image

Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 24

overflow. At initial fill (for system volume calculations) the deaerator and

cold seal sections must be filled completely and the expansion section

must be filled to a level of 4 inches to "make" the liquid level switch.

2. The volume between the initial fill level and the safe "full" level is the

amount available for expansion. That volume is used to decide which

tank is suitable for the system expansion.

f) Sizing

Example

1. A system contains 175 gallons, including the heater, but not the tank.

You select the FT-200-L, so you add 25 gallons to 175. You must look up

the expansion rate for the thermal fluid. (Assume it is 25%). 200 gal. x

1.25 = 250 gallons. 250-200 = 50 gallon expansion. The FT-200-L has

only 46 gallons available for expansion, so the correct selection is the

FT-500-L.

g) Location

1. The tank must be installed in accordance with Fulton Thermal

Corporation's specifications.

2. Unless the system is pressurized, the inlet to the deaerator section must

be higher than or equal to the highest point in the system to prevent

pockets of air from collecting in system piping.

3. The head required at the circulation pump suction inlet must also be

taken into account to avoid the possibility of pump cavitation. In systems

operating close to maximum fluid temperature, the tank must be elevated

enough, possibly well above the highest point in the system to prevent

pump cavitation by increasing the static head. An inert pressurizing

blanket may be considered as an alternative. See Pressurized

Systems.

4. Supports for tank mounting should be provided by the client/contractor.

These should be suited for supporting the tank by the side rails. The

eyelets fitted to the tank are for lifting only.

Advertising