Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 35

Recommended Loads for Flexitallic Spiral Wound Class 300# Gaskets

SAE Grade 5 Bolts (typical) or Equal

Nominal Flange Size

Inches

Number of Bolts

Diameter of Bolts

Inches

Preferred Torque

Required per Bolt

Ft-Lbs.

1/2 4 1/2 45
3/4 4 5/8

90

1 4 5/8

90

1 ¼

4

5/8

90

1 ½

4

3/4

150

2 8 5/8

90

2 ½

8

3/4

150

3 8 3/4

150

3 ½

8

3/4

150

4 8 3/4

150

5 8 3/4

150

6 12 3/4

150

8 12 7/8

240

10 16 1 368

Note

The system pump is not to be used to fill the system.

The system is usually filled from the lowest point, with the aid of a pump. On skid-

mounted units, a drain and fill connection is provided in the inlet piping to the

pump.

18. Heater Connections

a) The outlet of the pump should connect directly to the inlet of the heater via an isolating

valve and pump flexible connector.

b) The heater outlet should be piped directly to the system, via an isolating valve.

Drain and Fill Connection