Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 41

Note

Fulton Thermal Corporation cannot be held responsible in the case of accident or

damage resulting from the use of inadequate fluid.

i)

Routine Analysis of Heat Transfer Fluid

1. Nearly all leading manufacturers of heat transfer fluids provide an after

sales service to monitor the condition of the fluid in operation and make

recommendations when replacement becomes necessary.

2. Each fluid manufacturer has procedures for regular testing and analysis

of the fluid. These usually allow for a sample to be taken and analyzed at

least once a year, although actual frequency will depend on operating

temperature, number of hours operated weekly, and the results of tests

made during the first weeks of system operation.

3. Fulton Thermal Corporation recommends that the thermal fluid in your

system be analyzed within the first two months after start-up.

4. During the first few months of operation, sampling may be carried out at

frequent intervals to confirm that system performance has been

predicted correctly.

5. If the supplier of your thermal fluid does not contact you within four

weeks of commissioning, contact the supplier and make certain that the

“fill” is registered for routine analysis.

j)

Thermal Fluid Breakdown

1. The possibilities of thermal fluid breakdown are very slim in a typical

closed loop thermal fluid system. Fulton’s D/A tank creates a “cold seal”

of fluid that is slightly above ambient temperature. This prevents

oxidation that will happen when high temperature fluid contacts air.

2. This will also occur when hot thermal fluid contacts air at a leak in the

system piping. Oxidized thermal fluid becomes acidic and will damage

the thermal fluid system. Thermal fluid breakdown can occur in sections

of piping where there is a low flow

condition. A low flow rate through the heater will result in high film

temperatures leading to breakdown of the thermal fluid.

3. Multiple pressure switches and a differential pressure switch are used to

prevent this condition from occurring. These safeties must not be

bypassed at any time.