Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 16

2. Placement

a) Proper placement of your Fulton Thermal Fluid Heater is essential. Attention paid to the

following points will save a great deal of difficulty in the future. Correct placement is the

first step to trouble-free installation, operation and maintenance.

3. Location

a) Authorities with jurisdiction over any national or local codes which might be applicable to

thermal fluid applications should be consulted before installations are made.

b) The heater should be located as close as possible to the place where the heat will be

used in order to keep pipe work costs to a minimum.

c) A level, hard, non-combustible surface is required for a suitable base for mounting the

unit. It is suggested that a four inch curb be installed completely around the unit. In the

event of a large spill, this will help contain the fluid.

d) Approximations for the floor loading of each heater are given in the floor loadings table.

Check building specifications for permissible floor loading.

e) The heater should be placed in a suitable heater house or well ventilated separate room

through which personnel do not normally pass. This is not essential, but the layout should

eliminate traffic in potentially hazardous areas. For instance, the service engineer or the

operator should not have to pass exposed, hot pipe work to make adjustments to the

heater controls.

f) Ventilation must be sufficient to maintain a building temperature of 100°F. or less and the

panel box temperature must not exceed 125°F. Natural ventilation should be provided by

means of grills at floor and ceiling level.

4. Access

a) Access around the heater should be provided to facilitate maintenance. Appropriate

clearances for all sides follow.

b) Place heater with clearances to unprotected combustible materials, including plaster or

combustible supports, not less than the following:

Heater Front

36”

(1 m)

Heater Sides

18”

(.5 m)

Heater Rear

18”

(.5 m)

Heater Top

66”

(1.67 m)

(For element removal)

5. Approximate Floor Loadings