a) Manually check fluid level in the expansion tank. Drain ½ gallon of thermal fluid from the

expansion tank. If water is present, continue to drain ½ gallon until no water is present.

b) Check operation of all safeties. Refer to the instructions at the end of this section.

c) Review daily log sheets noting any deviations from the norm.

d) Check the tightness of all couplings, including the fuel oil pump drive (oil-fired units), fan

impeller, circulating pump, etc.