Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 46

Some plastics can be dissolved by thermal fluid.

Note

Do not use system circulating pump for system filling.

Note

A pump that has been used for water or a different thermal fluid should not be

used prior to extensive cleaning. Thermal fluid can be damaged by contact with

moisture or other fluids.

Warning

Pressurizing a drum to force fluid into the system is not recommended. The drum

can easily explode, creating a hazard to personnel and equipment.

d) Filling

Procedure

1. Fill the system slowly, closing all opened bleed and drain valves as fluid

reaches them.

2. When the fluid reaches and flows from the expansion tank low level

manual test connection, begin slowing down the filling process.

3. Close the low level connection and continue to fill until the liquid level

switch closes. After fluid appears in the low level connection, only a small

amount of additional fluid should be required.

4. If fluid is observed coming from the expansion section high level manual

test connection, drain fluid from the tank until the level is between the

liquid level switch and the high level connection.

5. Filling is complete when the fluid has reached the lowest level in the

expansion tank required to actuate the liquid level switch. Check to see

that the liquid level switch operates freely. To confirm operation of the

Drain and Fill Connection