Fulton Vertical Electric (FT-N) Thermal Fluid (hot oil) Heater User Manual

Page 26

Advertising
background image

Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 26

10. Connections

a) The vent connection must be made in a manner that will prevent penetration of water or

foreign bodies into the tank. This connection must always terminate in a safe, well

ventilated area and has to be free of obstruction, open to atmosphere, and arranged in

such a manner that, in the event of discharge from the system, thermal fluid could drain

into a catch tank without danger to personnel or property.

Note

Non-code tanks cannot be pressurized over 15 psig.

Warning

High temperature thermal fluid, steam and combustible vapors may be vented

through this connection.

b) The vent run should be the same size as the tank outlet. It should run pitch down from

the outlet of the tank to the catch tank.

c) If nitrogen is used on the system, the vent can be reduced and should be piped with a

positive closing valve at the catch tank.

Liquid Level

Switch