6.2 Main Power Board Connections (continued)

D. Connect the three AC main power wires (Phases A, B and C) to their respec-

tive positions as labeled on terminal block TB1. After all conductors are con-

nected to each of their respective terminal block positions and tightened to 7

in-lb, verify that each terminal block screw is securely fastened by gently tug-

ging on each conductor. Verify that no conductor wires are frayed or shorting

to adjacent terminal block positions.

E. Turn ON the AC main power input. The meter display will light up and scroll

through 6 displays. Each display is visible for 5 seconds. Display screens are

as follows:

Screen 1 - Total kilowatt-hours (kWh) consumed

Screen 2 - Peak demand (kW) with date & time stamp

Screen 3 - Actual load (kW)

Screen 4 - RMS Amps

Screen 5 - RMS Volts Phase to Neutral

Screen 6 - RMS Volts Phase to Phase

Screen 7 - Power factor (PF) per phase

F. Verify the voltage readings on Screen 5 using an AC voltmeter. Typical read-

ings shown below are measured phase to neutral (L-N) for 4 wire and phase

to phase (L-L) for 3 wire. Readings should be +/- 10% of nominal.

NOTE: Meters are powered by phases A and B. The displayed voltages will be the

measured AC voltage between phases.

Meter Type

Nominal Voltage

Limits (+/- 10%)

208V, 3ø, 4 Wire

120 VAC (L-N)

108 to 132 VAC

480V, 3ø, 4 Wire

277 VAC (L-N)

249 to 305 VAC

600V, 3ø, 4 Wire

347 VAC (L-N)

312 to 380 VAC

240V, 3ø, 3 Wire

240 VAC (L-L)

216 to 264 VAC

480V, 3ø, 3 Wire

480 VAC (L-L)

432 to 528 VAC