4 current sensor installation & wiring – E-Mon E32-6003200REZ7KIT User Manual

Page 16

Advertising
background image

CLASS 3200 METER

62-0390-02

16

6.4 Current Sensor Installation & Wiring

Once the AC voltages have been confirmed to be within acceptable limits, you are

ready to install the current sensors. TB2 is the input for Phase A, TB3 is the input for

Phase B and TB4 is the Phase C input.

The Class 3200 meter can be used with two types of current sensors:

1. Split-core current sensor. This sensor opens so that it can be attached around

the circuit being monitored without interrupting power.

2. Solid-core current sensor. This sensor does not open and requires the monitored

conductor to be removed from the circuit to install the current sensor. This type is

only supplied when specified at time of order.

NOTE: It is recommended that a UL listed current sensor be used for this application.

6.4.1 Installing the Split-Core Current Sensor Assembly

1. Each phase being monitored will require one two-piece current sensor assembly.

Open the two-piece current sensor assembly by releasing the nylon clamp using

a flathead screwdriver.

Fig. 6. Split Core Sensor.

2. Reassemble the current sensor assembly around the conductor(s) to be moni-

tored. Ensure the current sensor halves marked “Load” are both facing the load

side of the conductor. The colored arrow will be on the source side of the con-

ductor being monitored and MUST be pointed in a clockwise direction around the

conductor being monitored. Tighten the nylon clamp to complete the assembly.

Fig. 7. Split Core Sensor.

IMPORTANT:

When looking from the source side of the conductor(s) being monitored, you

should see the arrow on the current sensor assembly. The arrow should be

pointing in a clockwise direction around the conductor(s) being monitored. If

the arrow is not positioned on the source side, inaccurate readings will result.

M33213

LOAD

SOURCE