2 external modem, 3 baud rate selection – E-Mon E32-6003200REZ7KIT User Manual

Page 26

Advertising
background image

CLASS 3200 METER

62-0390-02

26

6.9.2 External Modem

1. All meters should be connected to the RS-232 key as described in 6.8.2.

2. DISCONNECT POWER TO THE RS-232 KEY. Remove the cover by removing

the 2 screws from the bottom of the enclosure.

3. On the circuit board, locate the blue jumpers J7 (MODEM) and J8 (ex-MODEM).

If these jumpers are set in the DIRECT position, you must move the jumpers so

they are set in the MODEM position. Replace the cover and secure the enclo-

sure.

4. Connect the RS-232 key to the external modem using the supplied 8-conductor

flat modular cable.

5. Connect the 9VDC adapter to the power input on the back of the RS-232 key

and plug it into a 120VAC outlet.

IMPORTANT:

The modem should use a phone line that is dedicated exclusively to the AMR

system. Do not use a phone line that is shared by another modem or fax

machine.

6.9.3 Baud Rate Selection

The communication Baud rate on the Class 3200 meter is set through positions 3 and

4 on DIP switch S2 on the meter circuit board. The default is 9600 Baud.

1. Select 9600 when using the Class 3200 meter with a modem.

2. The Baud rate on the meter must always match the Baud rate selected in the E-

Mon Energy software; otherwise, communications will not function.

3. After a Baud change, press the CPU reset button to register the change.

4. All meters in the daisy-chain circuit must be set at the same Baud rate.

Fig. 15. Baud Rates.

M33195

BAUD RATE

SELECTION

SWITCHES

3

4

BAUD RATE

ON

ON

9600

OFF ON

19200

ON OFF

38400

OFF OFF

76800