E-Mon E32-6003200REZ7KIT User Manual

Page 43

Advertising
background image

43

62-0390-02

This special high voltage meter installation shows the correct wiring procedure for 4-

wire high voltage circuits. In this application, the 3 element meter connection is used

on the secondary circuits of the user supplied high voltage PTs and CTs.

The E-MON meter used in this application is the model E34-12025HV kWh meter.

Installation of these meters requires the use of three (3) current sensors mounted on

the secondaries of the high voltage Current Transformers. See the drawing above for

proper wiring. For correct operation, the meter must be installed correctly.

This special high voltage meter installation utilizes high voltage PTs (Potential

Transformers) and CTs (Current Transformers) supplied by others. The E-MON meter

is installed using the secondary outputs of these devices.

High voltage PTs reduce the primary voltage (4160v, 13200v, etc.) to a Secondary

output of 120v. This secondary is connected to the E-MON meter voltage inputs as

shown in the wiring diagram. High voltage CTs reduce the primary current (amps) to a

directly proportional 0~5 amp output. As an example, a 0~400 amp primary becomes a

0~5 amp proportional signal from the secondary output. This allows much smaller

wiring to be utilized in the meter hookup. The high voltage CT secondary is installed as

a continuous “loop”, with a single lead connected to both secondary terminals.

E-MON meters accept a 0~2 volt signal from their Current Sensors. To convert the 0~5

amp signal, the Current Sensors are installed on the CT secondary lead. A set of 25

amp sensors is used in this application. These sensors have the high voltage CT

secondary lead passed through them five (5) times by looping the wire as shown in the

drawing. This allows a direct conversion of the CTs primary current to a directly

proportional 0~2 volt signal, which is used by the meter.

Since there is a signal ratio introduced by the high voltage CTs and PTs, it will be

necessary to multiply the number on the meter’s display for a correct reading. The

meter multiplier is calculated by using the CT ratio and the PT Ratio. [PTr x CTr /

Number of Secondary Lead Passes Through Sensor]. The E-MON 25 amp HV kWh

meter with 5 wraps of the high voltage CT secondary will have its multiplier calculated

by the formula shown below.

EXAMPLE: CT = 400:5 = 80:1 (CTr = 80)

PT = 4200:120 = 35:1 (PTr = 35)
Wraps (Passes) = 5

METER MULTIPLIER

= PTr x (CTr/Wraps)

35 x (80/5)
35 x (16) = 560

Advertising