E-Mon E32-6003200REZ7KIT User Manual

Page 47

Advertising
background image

47

62-0390-02

BACnet Object Descriptors: CL3200

Instance

ID

BACnet

Object

Description

Units

BACnet

Property

CL

3200

1

1

Analog

Input

Energy delivered

kWh

Present Value R

2

1

Analog

Input

Energy received

kWh

Present Value R

3

1

Analog

Input

Reactive energy delivered

kVARh

Present Value R

4

1

Analog

Input

Reactive energy received

kVARh

Present Value R

5

Analog

Input

Real power

kW

Present Value R

6

Analog

Input

Reactive power

kVAR

Present Value R

7

Analog

Input

Apparent power

kVA

Present Value R

8

Analog

Input

Power factor

% PF

Present Value R

9

Analog

Input

Peak demand

kW

Present Value R

10

Analog

Input

Current average

Amps

Present Value R

11

Analog

Input

Voltage line-neutral

Volts-N

Present Value R

12

Analog

Input

Voltage line-line

Volts-L

Present Value R

13

Analog

Input

Frequency

Hz

Present Value R

14

Analog

Input

Phase angle

Degree

Present Value R

15

Analog

Input

Real power phase A

kW

Present Value R

16

Analog

Input

Real power phase B

kW

Present Value R

17

Analog

Input

Real power phase C

kW

Present Value R

18

Analog

Input

Reactive power phase A

kVAR

Present Value R

19

Analog

Input

Reactive power phase B

kVAR

Present Value R