0 meter technical specifications – E-Mon E32-6003200REZ7KIT User Manual

Page 8

Advertising
background image

CLASS 3200 METER

62-0390-02

8

3.0 METER TECHNICAL SPECIFICATIONS

Ordering Information: Define brand, class, input voltage, amperage, protocol, and

sensor type in the format A-BB-CCC-DDDD-E-FFF-GGG, where

A = Brand: E for E-Mon

BB = designates Class: 3200 (32), 3400 (34), or 5000 (50) meter

CCC = input voltage: (208, 480, 600, 120 volt for High Voltage)

DDDD = current rating: (100, 200, 400, 800, 1600, 3200, 25HV)

E = enclosure: J = metal (type 1), R = non-metallic (type 4X), M = MMU

FFF= protocol: RTU = Modbus, BAC = BACnet, EZ7 = proprietary

GGG = Sensors: KIT = split-core, SCS = solid-core, “blank” = none supplied

Input Voltage

Configuration

3-wire (delta) Or 4-wire (wye)

Mains Voltage Input Up To 600 VAC RMS available
Input Power

6 VA maximum rating

Current Sensor

Rating

Up To 3200 amps RMS AC available

Power Factor

0.5 leading or lagging

Line Frequency

50-60 Hz

Metering Accuracy

ANSI C12.20

Temperature Range -20C to +50C
Relative Humidity

Range

0-95% non-condensing

Altitude

2000 meters maximum

Voltage Overload

+25% continuously: +100% For 20 cycles

Current Sensor

Overload

100% for 1 minute

Pollution Degree

Degree 2 in accordance with IEC 664

Installation

(Overvoltage)

Category

Category III

Measurement

Category

Category III

M33191

EXAMPLE:

E 32- 208 200 J RTU KIT

E-MON

CLASS 3200 METER

INPUT VOLTAGE (208V)

CURRENT RATING (200A)

ENCLOSURE (METAL - TYPE 1)

PROTOCOL (MODBUS)

SENSORS (SPLIT-CORE)