CLASS 3200 METER

62-0390-02

28

6.11 BACnet MS/TP Wiring

BACnet MS/TP wiring is the same as Modbus and EZ7 wiring. See Sections 10 and 11

for instructions on changing I.D. and IP addresses.

6.12 Connecting Class 3200 Meters to USB Key using

RS485

The USB Key plugs into the PC’s USB port and provides a termination point for the

RS485 wiring from the meters. Up to 52 meters can be “Daisy chained” with up to 4000

feet total RS485 wiring. The USB Key is labeled for “plus (+)”, “minus (-)“, and ground

and the wiring must match the same positions on the meters. If more than 52 meters

are to be monitored, additional USB Keys can be utilized to connect them to the PC.

Fig. 17. Connecting Class 3200 Meters to the USB Key using RS485.