0 high voltage metering – E-Mon E32-6003200REZ7KIT User Manual

Page 41

Advertising
background image

41

62-0390-02

11.0 HIGH VOLTAGE METERING

kWh Meter Installation Instructions for Use with E-MON

Meters in High Voltage Applications

The E-MON model # E34-12025HV kWh meter is designed to be used for monitoring

high voltage (2400, 4160, 13200, etc) circuits, either “stand alone” or in an AMR

application.

This meter is intended to be used with the appropriate high voltage Potential

Transformers (PTs) and Current Transformers CTs) supplied by others. The meter

application is centered around a 120 VAC secondary output from the high voltage PTs

and a 5 amp secondary output from the high voltage CTs.

Items addressed by this document include the installation of the E34-12025HV kWh

meter on high voltage circuits as well as the calculations to provide the correct meter

multiplier based on the PT and CT sizes used on the high voltage conductors.

Installation should be performed by qualified personnel and only according to all

applicable electrical codes.

High Voltage CTs (supplied by others) reduce the primary current (amps) to a directly

proportional 0~5 amp secondary output. As an example, a 0~400 amp primary

becomes a 0~5 amp proportional signal from the secondary output. In our application,

the high voltage CT secondary is installed as a continuous “loop”, with a single

conductor connected to both secondary terminals.

To convert the 0~5 amp signal to a 0~ 2 volt signal, E-MON’s Current Sensors are

installed on the CT secondary conductor. A set of 25 amp sensors is used in this

application. These sensors have the high voltage CT secondary conductor passed

through them five (5) times (see below) by looping the secondary conductor as shown

in the drawing. The reason for this is so that the 5 amp secondary now appears to the

current sensor as a 0~25 amp signal. This creates a conversion of the CT’s primary

current to a directly proportional 0~ 2 volt signal which is utilized by the E-MON meter.

The example from the first paragraph has now become a 400 amp to 2 volt device, by

this technique.

Advertising